Kaiyi — 14.8.1 RUN and NET Indicators

Chapter 14 Remote I/O Communication Module AHRTU-PFBS 14.8 LED Indicator and Trouble-shooting 14.8.1 RUN and NET Indicators  RUN LED RUN LED displays the work status of AHRTU-PFBS-5A.  NET LED NET LED displays if the connection between AHRTU-PFBS-5A and the PROFIBU DP master is normal. 14-49 LED state Indication How to deal with Green light ON AHRTU-PFBS-5A is in RUN state and is communicating with the master. -- Green light flickers AHRTU-PFBS-5A is in STOP state and has not made the connection with the master (When the digital display shows F1.) 1. Turn the RUN/STOP switch of the master PLC to RUN 2.

Check if AHRTU-PFBS-5A has been configured in the PROFIBUS DP master configuration software. 3. Check if the communication cable between the PROFIBUS DP master and AHRTU-PFBS-5A is normal. 4. Check if the PROFIBUS DP master works normally. 5. Verify that both of the two ends of the PROFIBUS DP network have the terminal resistors. Green light OFF No power Check if the power module PS05 works normally. LED state Indication How to deal with Green light ON The master makes the connection with the slave. -- Red light ON AHRTU-PFBS-5A does not make the connection with the master (while reporting F1) or is offline after making the connection with the master (while reporting F6) 1.

Check if AHRTU-PFBS-5A has been connected to the PROFIBUS DP bus 2. Check if the communication cable between the PROFIBUS DP master and AHRTU-PFBS-5A is normal. 3. Check if the actual address of AHRTU-PFBS-5A is consistent with that configured in the software. 4. Check if the GSD file used is correct. Green light OFF No power Check if the power module PS05 works normally.