Kaiyi — 14.8.2 Digital Display

AH500 Module Manual 14.8.2 Digital Display  The digital display displays the status of AHRTU-PFBS-5A. 14-50 Code Indication How to deal with 1~ 7D When AHRTU-PFBS-5A works normally, the digital display displays its node address. -- 80 AHRTU-PFBS-5A is in STOP status. Turn the RUN/STOP switch of the master PLC to RUN. F0 The node address of AHRTU-PFBS-5A exceeds the valid range. Set the node address of AHRTU-PFBS-5A between 1~125. F1 1. AHRTU-PFBS-5A has not been connected to the PFOFIBUS-DP network. 2. The PFOFIBUS-DP master has not configured AHRTU-PFBS-5A 1. Check if AHRTU-PFBS-5A has been configured to the PROFIBUS DP master configuration software. 2.

Check if the communication cable between the PROFIBUS DP master and AHRTU-PFBS-5A is normal. 3. Check if the PROFIBUS DP master works normally. 4. Check if the two terminal nodes at both ends of the PROFIBUS DP network have been added with the terminal resistors. F2 Parameter error Check if the GSD file AHRTU-PFBS-5A is using is correct. F3 1. An configuration error 2. No configuration of I/O modules for AHRTU-PFBS-5A 1. Check if the GSD file AHRTU-PFBS-5A is using is correct. 2.

Check if the I/O modules for AHRTU-PFBS-5A are configured in the Profibus DP configuration software F4 An error in initialization of AHRTU-PFBS-5A Contact the factory if the error still exists after AHRTU-PFBS-5A is repowered. F5 An error in internal memory units Contact the factory if the error still exists after AHRTU-PFBS-5A is repowered. F6 AHRTU-PFBS-5A loses the communication with the master. Check if the communication cable between the PROFIBUS DP master and AHRTU-PFBS-5A is normal. E4 Inconsistency between the actual I/O modules connected to the rack and those configured via the software 1.

Check if the actual I/O modules connected to the rack are consistent.with those configured via the software. 2. Check if any I/O module connected to the rack is damaged or does not exist. E5 1. An error in an extension rack 2. The actually connected rack is not consistent with that configured in the software. 1. Check if the extension rack communication cable is connected properly. 2. Check if the extension rack is normal. 3. Check if the actually connected rack is consistent with that configured in the software. E6 An error alarmed from the modules connected to AHRTU-PFBS-5A 1. Check if there is any error in the module hardware. 2. Check if the power supply works normally. 3.

Check if the input signal exceeds the hardware range.