Chapter 14 Remote I/O Communication Module AHRTU-PFBS When the input/ output mode of the analog module is positive voltage or positive current, the corresponding digital value is 0 ~32000; for example, if the modes are 0V~10V and 4mA~20mA, the corresponding digital values are both 0~32000. When the input /output mode of the analog module is negative voltage or negative current, the corresponding digital value is -32000~32000; for example, the modes are -10V~+10V, and -20mA~20mA, the corresponding digital values are both -32000~32000. Pick “AH08DA-5B” and the related parameters are displayed as follows. The output modes of CH0~ CH3 are all set to -10V~+10V.
Double click the parameters in “Name” column. The setting value can be revised directly if the mouse arrow becomes the “I” symbol. And select hexadecimal or decimal as Display mode. 14-67