Kaiyi — 14.9.4 Configuration of the Master

AH500 Module Manual Explanation of the options above The conversion between the analog quantity and digital quantity for all modules that AHRTU-PFBS-5A supports: When the input/ output mode of the analog module is positive voltage or positive current, the corresponding digital value is 0 ~32000; for example, if the modes are 0V~10V and 4mA~20mA, the corresponding digital values are both 0~32000. 14-68 Name Setting Explanation rack 0x02 The number of the rack where the I/O module are placed (Rack number is 1~8, 1 represents the main rack, 2~8 are extension racks and the slot number is 0~11.) slot 0x02 The number of the slot on the rack where the I/O module is.

(Rack number is 1~8, 1 represents the main rack, 2~8 are extension racks and the slot number is 0~11). CH0~CH7 Output mode disable -10V~+10V 0V~10V 5V~+5V 0V~+5V 1V~+5V The output channel mode of AH08DA-5B is disabled by default. Mode: disable Mode: -10V~+10V Mode: 0V~10V Mode: -5V~+5V Mode: 0V~+5V Mode: 1V~+5V CH0~CH7 output hold disable/enable Output hold options: Enable: the output of other I/O modules of AHRTU-PFBS-5A is held when some I/O module has a fault and the master is disconnected or stops running. Disable: the output of other I/O modules of AHRTU-PFBS-5A is cleared to 0 when some I/O module has a fault and the master is disconnected or stops running.