Chapter 15 CANopen Communication Module AH10COPM Status codes 15.5.3 Sending an NMT Command 1. Function block The AH10COPM-5A module which functions as a master station in a slot on the main backplane used can send an NMT command by means of the function block CANopen_NMT in ISPSoft. 2. Input pins/Output pins 15-27 Status code Description 0 No request for data transmission 1 The sending of the SDO is successful. 2 The SDO is being transmitted. 3 Error: SDO transmission timeout 4 Error: Illegal command 5 Error: The request message is illegal. 6 Error: The response message is illegal. 7 Error: The equipment which will send a message is busy. 8 Error: Illegal type 9 Error:
Incorrect node address 0A Error message (Please see the error code in the SDO response message.) Input pin Name Function Data Setting value Time when a value is valid type SID Slot number WORD K0~K11 The value of the SID input pin is valid when there is a transition in the Execute input pin’s signal from low to high. Execute The function block is executed when there is a transition in the Execute input pin’s signal from low to high. BOOL True/False - NodeID Node address WORD K1~K127 - Service Service type WORD 01 (Hex): Enabling a remote node 02 (Hex): Stopping a remote node 80 (Hex): Ready to operate 81 (Hex): -