AH500 Module Manual 15-28 Input pin Name Function Data Setting value Time when a value is valid type Resetting application 82 (Hex): Resetting communication Output pin Name Function Data type Time when there is Time when there is a transition in an output pin’s signal from high to low a transition in an output pin’s signal from low to high Done The execution of the function block is complete. BOOL There is a transition in the Done output pin’s signal from low to high when the execution of the function block is complete. There is a transition in the Done output pin’s signal from high to low when there is a transition in the Execute input pin’s signal from high to low.
If the Execute input pin is set to False when the execution of the function block is complete, the Done output pin will be set to False in the next cycle. Busy The function block is being executed. BOOL There is a transition in the Busy output pin’s signal from low to high when there is a transition in the Execute input pin’s signal from low to high. There is a transition in the Busy output pin’s signal from high to low when there is a transition in the Done output pin’s signal from low to high. There is a transition in the Busy output pin’s signal from high to low when there is a transition in the Error output pin’s signal from low to high.
There is a transition in the Busy output pin’s signal from high to low when there is a transition in the Aborted output pin’s signal from low to high. Error An error occurs in the function block. BOOL An error occurs when the function block is executed. There is a transition in the Error output pin’s signal from high to low when there is a transition in the Execute input pin’s signal from high to low.