Kaiyi — 15.6.2 Error Codes

AH500 Module Manual  ERROR LED indicator Difference between the red light which flashes once and the red light which flashes twice: ON The red light flashes once. OFF ON The red light flashes twice. OFF 15.6.2 Error Codes Users can monitor the error codes in the system log in ISPSoft, or the error code in the module error code register in the AH500 series CPU module used.  AH10COPM-5A functions as a master station. 15-36 LED indicator Description Solution The light is OFF. AH10COPM-5A is normal. No action is needed. The red light flashes once. Bus fault 1. Check whether the CANopen bus cable used is a standard cable. 2.

Check whether the both ends of the CANopen bus used are connected to terminal resistors. 3. Check whether the noise around the CANopen bus cable used is strong. The red light flashes twice. Master station: The control of the errors in a slave station is not sent after a set period of time. Slave station: AH10COPM-5A does not send a heartbeat message after a set period of time. 1. Check whether the CANopen bus cable used is a standard cable. 2. Check whether the both ends of the CANopen bus used are connected to terminal resistors. The red light is ON. The bus used is off. 1. Check whether the bus cable on the CANopen network created is connected correctly. 2.

Check whether the serial communucation speed of AH10COPM-5A is the same as the serial communication speeds of other slave stations. 200 ms 200 ms 1000 ms 200 ms 200 ms 200 ms 200 ms 200 ms 1000 ms 200 ms 1000 ms Code Description Solution 16#A0E0 AH10COPM-5A receives an emergency message from a slave station. Use the function block CANopen EMCY to read relevant _ information. 16#A0E1 The length of a PDO that a slave station sends is not the same as the length of the PDO set in the node list. Set the length of the PDO in the slave station again, and then download the setting to AH10COPM-5A.