Chapter 15 CANopen Communication Module AH10COPM 15.6 Error Diagnostics and Troubleshooting 15.6.1 LED Indicators and Troubleshooting AH10COPM-5A has two LED indicators—a RUN LED indicator and an ERROR LED indicator. The LED indicators indicate the current states of the module.  RUN LED indicator Difference between the green light which flashes once and the green light which blinks: ON The green light flashes once. OFF ON The green light blinks. OFF 15-35 LED indicator Description Solution The light is OFF. AH10COPM-5A is disconnected. Check whether the AH500 system used is powered. The green light flashes once. AH10COPM-5A stops running.

AH10COPM-5A is downloading a network configuration, and waits to complete the downloading of the network configuration. The green light blinks. AH10COPM-5A is ready to operate. If the green light is blinking when the AH500 series CPU module is running, users have to 1. check whether the bus cable on the CANopen network created is connected correctly. 2. check whether the serial communication speed of the master station selected is the same as the serial communication speeds of the other slave stations. 3. check whether the slave stations configured are connected to the network created. 4. check whether slave stations are offline. The green light is ON. AH10COPM-5A is operational.