Kaiyi — 16.4.3 RTU Input Register

Chapter 16 Remote I/O Module AHRTU-ETHN-5A 16.4.3 RTU Input Register 16-11 Number Attribute Name Description b1 b2 0: Stop, 1: In operation b3 0: No module exists. 1: The module exists. b4 0: Inconsistent with the software configuration. 1: consistent with the software configuration. SR21~28: The states of I/O modules 0~7 on the extension backplane 1 SR29~36: The states of I/O modules 0~7 on the extension backplane 2. And so on… 77 R RTU error code Refer to Troubleshooting in section 16.7. 78-89 R Error codes of I/O modules on RTU’s main backplane Display the error codes of I/O modules 0~11 on the main backplane. For details, refer to the explanation of error codes in modules.

90-145 R Error codes of I/O modules on RTU’s extension backplanes 1~7 Display the error codes of I/O modules 0~7 on the extension backplane 1~7. SR90~97: The error codes of I/O modules 0~7 on the extension backplane 1 SR98~105: The error codes of I/O modules 0~7 on the extension backplane 2. And so on… For details, refer to the explanation of error codes in modules. Number Attribute Name Description 0 R Status 0: Normal, 1: Alarming, 2: In error, 3: A fault exists but the module does not stop working. 1 R Reserved 2 R Error code Error code in AHRTU 3~10 R Reserved 11~15 R I/O module status The status of every I/O module is expressed with one bit. (0: normal operation; 1:

abnormal) Bit0 of number 11 stands for I/O module 0 on the main backplane. Bit 1 of number 11 is I/O module 1 on the main backplane and Bit 11 of number 11 is I/O module 11 on the main backplane. Bit 12 of number 11 indicates I/O module 0 on the extension module and so on.