Mitsubishi — 5.6 Descriptions of the Applied Instructions

Chapter 5 Applied Instructions  S : Timer; m : Time; D : Annunciator  The instruction ANS is used to drive an annunciator.  S : T0~T183 Explanation m : K1~K32,767 (Unit: 100 ms) D : S912~S1023 See the explanation of ANR for more information.  The instruction supports V devices and Z devices. (If the 16-bit instructions used, Z devices can not be used. If the 32-bit instruction is used, V devices can not be used.)  If X0.3 is ON for more than 5 seconds, the annunciator S999 will be ON. Example Even if X0.3 is turned OFF, S999 will still be ON.

(However, T10 will be reset to OFF, and the value of T10 will be 0.) X0.3 5-67 API Instruction code Operand Function 46 ANS P S, m, D Driving an annunciator Device Xn.n Yn.n M S K 16# F KnM KnS D W T C V Z S           m    D       Pulse instruction 16-bit instruction (7step s) 32-bit instruction   – ANS T10 K50 S999