AH500 Motion Control Module Manual Explanation S : Source device; D : Conversion result The binary floating-point value in S is converted into a binary value. The integer part of the binary value is stored in D , and the fractional part of the binary value is dropped. The instruction is the opposite of API 49 DFLT. SM1064 is the zero flag in an Ox motion subroutine, and SM968 is the zero flag in O100. SM1065 is the borrow flag in an Ox motion subroutine, and SM969 is the borrow flag in O100. SM1066 is the carry flag in an Ox motion subroutine, and SM970 is the carry flag in O100.
SM1049 is the operation error flag in an Ox motion subroutine, and SM953 is the operation error flag in O100. If a conversion result is 0, a zero flag will be ON. If the fractional part of a conversion result is dropped, a borrow flag will be ON. If a converesion result is not in the range of -2,147,483,648 to 2,147,483,647, a carry flag will be ON. Example When X0.1 is ON, the binary floating-point value in (D21, D20) is converted into a binary value. The integer part of the binary value is stored in (D31, D30), and the fractional part of the binary value is dropped.
X0.1 5-92 API Instruction code Operand Function Converting a binary 129 D INT P S, D floating-point number into a binary integer Device Xn.n Yn.n M S K 16# F KnM KnS D W T C V Z S D Pulse instruction 16-bit instruction 32-bit instruction (5 steps) – DINT D20 D30