Chapter 5 Applied Instructions Timing diagram: The second motion follows the first motion. The second motion can not interrupt the first motion. First Execute1 Busy1 Done1 Second Test Execute2 Busy2 Done2 Motion Error2 Velocity Position After the first single-speed motion is complete, the second single-speed motion will be executed. After the execution of the motion control function block named FIRST is complete, the motion control function block named SECOND will be executed. The first axis moves for 25,000 pulses. The second single-speed motion is executed before the execution of the first single-speed motion is complete.
When Error2 is set to True, the first axis moves for 10,000 pulses. The motion control function block named SECOND is invalid. 5. Modules which are supported The motion control function block T_AbsSeg1 supports AH05PM-5A, AH15PM-5A, AH10PM-5A, and AH20MC-5A. 5.10.2 Relative Single-speed Motion 1. Motion control function block The motion control function block T_RelSeg1 is used to start relative single-speed motion. The 5-141