Mitsubishi — 13.5.1 Backup

Chapter 13 Expansion Storage Device  To restore, set bit 13 in SR214 to 0.  To backup devices, set bit15 in SR214 to 1. M1 For example, if the value in SR214 is 8000H, the file \AHMotion\Device\0.csv in a memory card will be restored to the motion control module. 13.5 Program Backup and Restoration 13.5.1 Backup The operation for a program backup is described below, 1. Monitor an AH500 series motion control module by PMSoft, and stop the operation under the monitoring. Alternatively, set SM072 to 0 to stop O100. 2. Set SR214 by a device monitoring table or external communication.  Set bit 12~bit 0 in SR214 to bit 0. The values of bit 12~bit 0 in SR214 represent a backup file name.

 To backup, set bit 13 in SR214 to 1.  To backup the program in the AH500 series motion control module, set bit 14 in SR214 to 1. After the program backup is completed, a .raw file which includes the password for the backup program will be generated in \AHMotion\Program\ in a memory card. The table above shows that the name of the .raw file is 0.raw. 13-7 MOV H8000 SR214