AH500 Operation Manual Description of the terminals *1. If the frequency of input signals received by an input terminal must be 200 kHz, the input terminal must be connected to a 1 kΩ (2 W) resistor in parallel. 2-75 Terminal Description Response Maximum input characteristic Curren t Voltage X0.0, X0.1, X0.8, X0.9, X0.12, and X0.13 1. They are single/A/B-phase input terminals. 2. The functions of the terminals: Motion control: X0.0 is the PG input for axis 1, and X0.1 is the PG input for axis 2. X0.12 is the DOG input for axis 1, and X0.13 is the DOG input for axis 2. X0.8 and X0.9 are for a manual pulse generator. High-speed count: X0.0 is the RESET input for counter 0.
X0.8 is the A-phase input for counter 0, and X0.9 is the B-phase input for counter 0. High-speed comparison and catch: The terminals can function as trigger signals for high-speed catches. Interrupt input terminals: X0.8, X0.9, X0.12, X0.13 100 kHz (*1) 15 mA 24 V Y0.8 and Y0.9 1. The high-speed pulse output terminals are transistors whose collectors are open collectors. 2. The functions of the terminals: Motion control: Y0.8 is the CLEAR output for axis 1, and Y0.9 is the CLEAR output for axis 2. High-speed comparison and catch: The high-speed comparison output terminals provide the PWM function. 200 kHz 15 mA 24 V Y0.0+, Y0.0-, Y0.1+, Y0.1-, Y0.2+, Y0.2-, Y0.3+, and Y0.3- 1.
They are differential output terminals. 2. The function of the terminals: Motion control: Y0.0+ and Y0.0- are the A-phase output terminals for axis 1. Y0.2+ and Y0.2- are the A-phase output terminals for axis 2. Y0.1+ and Y0.1- are the B-phase output terminals for axis 1. Y0.3+ and Y0.3- are the B-phase output terminals for axis 2. 1 MHz 5 mA 5 V