Delta Electronics AH500 — 7.5.2 Restoring the System

AH500 Operation Manual A system backup can be executed, whether a CPU module runs or stops. However, users have to make sure that the write protect tab on the left side of a SD card is slid upward before a system backup is executed. The system backup procedure is as follows. (1) Turn DIP switch 3 ON, and turn the other switches OFF. If users do not want to back up the values on the device memories, they need to turn DIP switch 4 ON. OFF ON OFF ON OR 1 1 Complete backup The values in the devices are not backed up. (2) Press the CLR button on the CPU module for five seconds. When the system backup is executed, the SYSTEM LED indicator blinks.

After the system backup is complete, the SYSTEM LED indicator is OFF. When the system backup is executed, the SYSTEM LED indicator blinks. 7.5.2 Restoring the System Before a system restoration is executed, users have to make sure that the backup file AUTOEXEC.dup is stored in a folder named SysDup in a memory card. After the system restoration is executed, the user program, the parameter setting, the hardware configuration, and the network configuration in the memory card are restored to a CPU module. In addition, if the data in the backup file includes the values on the device memories, the data restored to the CPU module will include the values on the device memories.

Before a system restoration is executed, users have to disconnect a CPU module. The system backup procedure is as follows. (1) Make sure that the CPU module is disconnected, turn DIP switch 2 ON, and turn the other switches OFF. OFF ON 1 7-8