Delta Electronics AH500 — 8.2.5.1 Ethernet─Advance: Filter

AH500 Operation Manual device A. Even if device B is assigned the same IP address, the CPU module does not respond to device B. The steps of setting the function are as follows. Sixteen groups of addresses at most can be listed in the table. (1) Select the Enable Static ARP Table checkbox, and then double-click an item which will be modified or added in the table. (2) Type an IP address and a MAC address in the Static ARP Table window. Finally, click OK . Take the tables below for example.

After the setting in the tables is downloaded to the CPU module, devices whose IP addresses are in the range of 192.168.1.1 to 192.168.1.50, and devices whose IP addresses are in the range of 192.168.1.100 to 192.168.1.150 are allowed to communicate with the CPU module if the CPU module operates. Besides, if the CPU module communicates with a device whose IP address of 192.168.1.20, the MAC address of the device must be BA:99:BA:14:BA:51. Likewise, if the CPU module communicates with a device whose IP address is 192.168.1.21, the MAC address of the device must be 00:10:5A:81:CA:FD. *1. The parameters set in HWCONFIG must be downloaded to the CPU module so that they can take effect.

(Please refer to section 8.2.6 or section 8.4.4 for more information.) *2. If users want to know the MAC address of a CPU module, they can click Online Mode in HWCONFIG to view the information about the CPU module (section 8.4.6), or click System Information in ISPSoft to get the information about the CPU module connected and the status of the CPU module (section 14.5.1 in ISPSoft User Manual). 8-39