Delta Electronics AH500 — 8.2.5.1 Ethernet─Advance: Filter

Chapter 8 Hardware Configuration *. The parameters set in HWCONFIG must be downloaded to the CPU module so that they can take effect. (Please refer to section 8.2.6 or section 8.4.4 for more information.) 8.2.5 Ethernet ─ Advance If a CPU module is equipped with an Ethernet port, users can enter this page. For example, AHCPU5xx-EN is equipped with an Ethernet port. After users click the Ethernet─Advance tab at the top of the window, they can set devices on a network. 8.2.5.1 Ethernet ─ Advance: Filter After users click the Ethernet─Advance tab at the top of the window, and the Filter tab at the bottom of the window, they can set a filter. Devices on a network are filtered.

The setting here ensures that objects communicating with the CPU module are devices which are allowed.  Enable IP Address Filter If the Enable IP Address Filter checkbox is selected, devices whose IP addresses are listed in the table will be allowed to communicate with the CPU module, and the CPU module will discard data packets sent from devices whose IP addresses are not listed in the table. The steps of setting the function are as follows. Sixteen groups of IP address at most can be listed in the table. (1) Select the Enable IP Address Filter checkbox, and then double-click an item which will be modified or added in the table.

(2) Type a start IP address and an end address in the IP address Filter window. The start IP address must be less than the end IP address. Finally, click OK .  Enable Static ARP Table Users can use this function to set MAC addresses and corresponding IP addresses. The MAC address of every device is unique. If the MAC address of device A is known, the MAC address can be bound to the IP address assigned to device A. The CPU module will regard the IP address as the exclusive address of 8-38