Chapter 8 Hardware Configuration The port number used by the local CPU module and the port number used by the remote device can not be the same, and the devices where data which will be sent is stored can not overlap the devices where data which will be received is stored. If the IP address of the remote device is 192.168.1.100, the port number used by the remote device is 65500, and the port number used by the local CPU module is 65501, the remote device and the local CPU module can transmit data through this TCP connection. If the local CPU module wants to send 10-word data to the remote device, the data will be stored in D0~D9 before the data is sent.
If the local CPU module receives 20-word data from the remote device, the data will be stored in D100~D119. If the length of data received is larger than the length set, the first 20-word data will be stored in D100~D119, and the data after the first 20-word data will be discarded. Likewise, if the length of data received is less than the length set, the data will be stored in the devices starting from D100, and the values in devices where no new data is stored will be retained. If no data is transmitted, and 60 seconds have elapsed, the CPU module will close the socket, and terminate the connection. *.
The parameters set in HWCONFIG must be downloaded to the CPU module so that they can take effect. (Please refer to section 8.2.6 or section 8.4.4 for more information.) 8.2.5.7 Ethernet ─ Advance: Web After users click the Ethernet─Advance tab at the top of the window, and the Web tab at the bottom of the window, they can enable the built-in web monitoring function of the CPU module. 8-48