Delta Electronics AH500 — 8.3.1 Managing the Version of a Module

Chapter 8 Hardware Configuration is clicked, the Transfer Setup window will appear. Users can select parameter types which will be downloaded in the window. Not all parameter types need to be downloaded to the CPU module. The Transfer Setup window is shown below. If the CPU checkbox or the Ethernet─Advance are selected, the CPU module must stop running during the downloading of the parameters. As a result, if the CPU module does not stop running, a dialog box will appear before the parameters are downloaded. After is clicked, all the PLC parameters will be uploaded. After *1.

If the name of the CPU module is different from the name attached to the model in the project management area, a dialog box will appear before the parameters are downloaded or uploaded. Please refer to section 8.2.2.1 for more information. *2. HWCONFIG adopts the communication setting in ISPSoft. Please make sure that ISPSoft is connected to the CPU module normally before the parameters are downloaded/uploaded. Please refer to section 2.4 in ISPSoft User Manual for more information. 8.3 Setting the Parameters in an AH500 Series Module 8.3.1 Managing the Version of a Module The functions of a module or the parameters in the module vary with the versions of the module.

In HWCONFIG, the functions of the modules and the parameters in the modules are defined in a document called MDS . When ISPSOft is installed, the latest MDS document is also installed. If a new version of the MDS document is released, users can download it or get the related file from an agent. An MDS document provides the information about the firmware versions of the modules. If users want to configure modules in HWCONFIG, they can select a suitable configuration according to the firmware versions of the actual modules. Besides, the parameters which can be set in the modules vary with the firmware versions of the modules which are set.

If the firmware version of a module set in HWCONFIG is older than the firmware version of the actual module, the module will operate normally after the parameters are downloaded. If the firmware version of a module set in HWCONFIG is newer than the firmware version of the actual module, the module will not operate normally after the parameters are downloaded. Please refer to the descriptions in the table below for more information. *. The compatibility mechanism described above only applies to modules whose firmware version is 1.0 or above. A firmware version below 1.0 is not compatible with firmware version 1.0 or above.

8-50 Difference Compatibility The firmware version set is older than the actual firmware version. The module operates normally. Functions or parameters not defined in HWCONFIG are assigned the default values. The firmware version set is newer than the actual firmware version. The module can not operate, and is in an erroneous condition. Users have to select a firmware version which is the same as the firmware version of the actual module in HWCONFIG, check the parameters, and download the parameters again.