Delta Electronics AH500 — 8.4.6.3 Changing the Status of a Module Online

Chapter 8 Hardware Configuration 8.4.6.3 Changing the Status of a Module Online If the hardware configuration is in the online mode, users can change the status of a module, carry out a simple test. cause damage to the system or staff.  Changing the operating state of a module If the hardware configuration is in the online mode, users can right-click a module, and click Run on the context menu. The module will begin to run. When the module runs, the green light on the module is ON. If the users click Stop on the context menu, the module will stop running. Besides, if the operating state of the CPU module is changed, the operating states of all the modules are also changed.

Before the status of a module is changed, users have to make sure that the operation does not  Changing the input/output state of a module If the modules which are configured include a digital I/O module, an analog I/O module, or a temperature measurement module, users can right-click the module, and click Module Status on the context menu. The users can monitor the input/output state of the module in the window which appears. In the window for a digital I/O module, users can right-click an input/output channel, and click Force ON or Force OFF on the context menu.

Before Force ON or Force OFF on the context menus is clicked, the CPU module and the digital I/O module must run to produce the actual outputs.  Force ON : The channel selected is forced ON.  Force OFF : The channel selected is forced OFF.  Release : The channel selected is not forced ON/OFF.  Release all : All the channels are not forced ON/OFF. 8-66