Chapter 11 Convenient Functions The limitation on data exchange performed by an AH500 series CPU module is described below. *. Maximum length of data which can be read/written (Reading data and writing data synchronously)=Maximum length of data which can be read/written (Reading data and writing data registers at most, and the data in 1600 contacts at most. If an AH500 series CPU module is a master station, DVP series PLCs can function as slave stations. DVP series PLCs can read data and write data simultaneously. asynchronously). A PLC which is not an AH500 series CPU module can read/write the data in 100 *. DVP series PLCs can modify the data length automatically.
11-23 Maximum length of data which Device Device range can be read/written Relays M0~M8191 450 registers/100 registers* 7200 contacts/1600 contacts* Data register D0~D65535 Link register L0~L65535 Maximum Maximum Maximum length of data which data register relay Communication can be read/written (word)* Device Model address address port which Reading and Reading and code which can which can supports RS-485 writing data writing data be used be used synchronously asynchronously ES 0x0000 D599 M999 COM2 100 100 EX 0x0001 D599 M999 COM2 100 100 SS 0x0002 D599 M999 COM2 100 100 EC 0x0003 D599 M999 COM2 100 100 EH 0x0004 D9999 M4095 COM2 100 100 SA 0x0006 D4999 M4095 COM2 100 100 SC 0x0007 D4999 M4095 COM2 100 100 SX 0x0008 D4999 M4095 COM2 100 100 SV 0x0009 D9999 M4095 COM2 100 100 EH2-L 0x000A D9999 M4095 COM2 100 100 EH2 0x000B D9999 M4095 COM2 100 100 ES2 0x000C D9999 M4095 COM2 and COM3 50 100 EX2 0x000D D9999 M4095 COM2 and COM3 50 100 SS2 0x000E D4999 M4095 COM2 50 100 SX2 0x000F D9999 M4095 COM2 50 100 SV2 0x0010 D11999 M4095 COM2 100 100 EH3-L 0x0011 D11999 M4095 COM2 and COM3 100 100 EH3 0x0012 D11999 M4095 COM2 and COM3 100 100 SA2 0x0013 D9999 M4095 COM2 and COM3 50 100 MC 0x0014 D9999 M4095 COM2 50 100 SE 0x0015 D11999 M4095 COM2 and COM3 50 100