AH500 Operation Manual Flowchart: Setting the parameters related to a PLC Link RST SM1595 S ET S M1595 Manually Automatically Assigning slave station addresses manually/automatically SM1595 Users assign station addresses to all the slave stations. The station addresses assigned to all the slave stations start from the station address in SR1756. S ET S M1585 RST SM1585 Automatically Manually Connecting to the slave stations manually/automatically SM1585 Users have to set the PLC Link flags. Users do not have to set the P LC Link flags.
Reading data and writing data synchronously/ Reading data and writing data asynchronously S 1598 M Manual mode Automatic mode PLC Link in the manual/ automatic mode Users have to set S R1338. Users have to set SM1586 to ON, and set SM1587 to OFF. Users have to set SM1586 to OFF, and set SM1587 to ON. Users have to set SM1568 to ON. 2. Example: The master station AHCPU530-RS2 is connected to slave station 1 DVP28SV11T. The data in the device 11-26