Delta Electronics AH500 — 11.1.3.2 Setting a PLC Link

Chapter 11 Convenient Functions addresses starting from D300 in slave station 1 is read into the device address starting from D100 in the master station. The number of data read from slave station 1 is 10. The data in the device addresses starting from D0 in the master station is written into the device addresses starting from D300 in slave station 1. The number of written into slave station 1 is 10. SM1598 is set to OFF, SM1595 is set to OFF, and SM1586 is set to ON. Users can check whether data exchange is preformed correctly by comparing the data in D0~D9 with the data in D100~D109 in the master station. Method 1:

Users can set the parameters related to a PLC Link according to the process described above. Step 1: Start ISPSoft, and write the program shown below. If M1 is turned ON, SM1586 and SM1584 will be ON. Step 2: Open the Monitor Table window in ISPSoft. Add M1, D0~D9, and D100~D109 to the window. Set 11-27