AH500 Operation Manual *1. If the master station automatically detects that the station address of a slave station is the same as its station address, it will not connect to the slave station. same as the device type used for writing. Otherwise an error will occur. 2. Descriptions of the read-only devices SM1588~SM1592: *2. If the reading of data and the writing of data are synchronous, the device type used for reading must be the 11-32 Device Name R/W Description SM1594 Detecting the slave stations automatically R/W The master station will detect the slave stations automatically only if the execution of the PLC Link stops. OFF:
The master station finishes detecting the slave stations, or waits to detect the slave stations. (Default) ON: The master station is detecting the slave stations. SM1595 Assigning slave station addresses automatically/manually R/W OFF: The station addresses assigned to all the slave stations start from the station address in SR1756. (Default) ON: Users assign station addresses to all the slave stations. SM1596 PLC Link error R If an error occurs when a PLC Link is executed, SM1596 will be ON. If no error occurs when a PLC Link is executed, SM1596 will be OFF. OFF: No error occurs. (Default) ON: An error occurs.
SM1597 Using an extension communication port R/W If SM1597 is ON, an extension communication port will be used to send a command. If SM1597 is OFF, a communication port on the master station is used to send a command. OFF: No extension communication port is used. (Default) ON: An extension communication port is used. SM1598 Enabling the function of reading data and writing data synchronously R/W If SM1598 is ON, t If SM1598 is OFF, t OFF: The function of reading data and writing data synchronously is disabled. ON: The function of reading data and writing data synchronously is enabled.*2。 Device Description SM1588 When the master station detects the slave stations automatically, SM1588 is ON.
When the master station finishes detecting the slave stations, SM1588 is OFF. SM1589 If SM1586 and SM1587 are ON, SM1589 will be ON, and SM1584 will be OFF. If no error occurs when the PLC Link is executed again, SM1589 will become OFF automatically. SM1590 If communication address error occurs when data exchange is performed, SM1590 will be ON. If no communication address error occurs when data exchange is performed, SM1590 will be OFF. SM1591 If a timeout occurs when data exchange is performed, SM1591 will be ON. If no timeout occurs when data exchange is performed, SM1591 will be OFF. SM1592 If the value in SR1338 is 0, SM1592 will be ON, and SM1587 will be OFF.
If the value in SR1338 is a legal value when SM1587 is ON, or if the value in SR1338 is a legal value when SM1584 is ON, SM1592 will be OFF.