Chapter 11 Convenient Functions 3. Descriptions of the special data registers SR1329~SR1338: 11.2 Ether Link (for AHCPU5X0 models) This function is applicable for AH500 basic CPU module series (AHCPU500/510/520/530). 11.2.1 Introduction of an Ether Link An Ether Link is a network mechanism for data exchange performed through an Ethernet connection. If there are several nodes in an Ethernet network, users can create a mechanism for data exchange in the network, and select a start mode. If the parameters which are set are downloaded to the PLCs in the network, the systems of the PLCs perform data exchange according to the start mode selected when the PLCs run.
The users do not have to write a redundant program. Besides, only AH500 series CPU modules support Ether Links. A PLC Link is a master/slave model. There is only one master station in an RS-485 network, and the other stations which are slave stations passively receive reading/writing commands from the master station. Compared with a PLC Link, an Ether Link adopts a safer data request mechanism. It is the data demanding nodes in an Ethernet network that execute an Ether Link. An Ether Link is not a master/slave model. It allows a node to send reading commands which ask for data to other nodes. The nodes will send the data to the node after they receive the reading commands.
Owing to the fact that a node can not send writing commands to other nodes, the use of an Ether Link is safer than the use of 11-33 Device Name R/W Description SR1332 Remote backplane ID R/W The value in SR1332 indicates the remote backplane on which the RTU module used is installed. The value in SR1332 must be in the range of 1 to 8. SR1333 Remote slot ID R/W The value in SR1333 indicates the remote slot in which the RTU module used is installed. The value in SR1333 must be in the range of 0 to 7. SR1334 Extension communication port number R/W The value in SR1334 indicates the communication port used. The value in SR1334 must be 1 or 2.
SR1335 Cycle of a PLC Link R The value in SR1335 indicates the time it takes for the master station to detect all the slave stations. (Time unit: 1 millisecond) The value in SR1335 will be 0 if one of the following conditions occurs. 1. The master station is turned from OFF to ON. 2. The master station begins to runs, or stops running. 3. The master station finishes detecting all the slave stations for the first time. The value in SR1335 will remain unchanged if the function of enabling a PLC Link is disabled. SR1336 Number of slave stations connected R Users can not set SR1336. The can only view the value in SR1336.
Whenever a PLC Link is executed, the slave stations connected to the master station are count. SR1337 Time for which data has been exchanged by means of a PLC link R The value in SR1337 indicates the number of times the master station exchanges data with all the slave stations. SR1337 can be used only if SM1587 is ON. If the execution of a PLC link stops, the value in SR1337 will not disappear. If the execution of a PLC link in the manual mode stops, the value in SR1337 will not disappear. If the value in SR1337 becomes the same as the value in SR1338, the execution of the PLC link in the manual mode will stop.
SR1338 Restricted time of the PLC link which is defined by users R/W Users can set the number of times the master station exchange data with all the slave stations. The value in SR1338 must be in the range of 1 to 65535. If the value in SR1338 is not in the range, it will not be changed automatically.