AH500 Operation Manual a PLC Link. Besides, all the nodes in an Ethernet network can send reading commands through TCP/IP, and the system automatically manages the transmission of packets through TCP/IP. Compared with a PLC Link, an Ether Link is more efficient. Data Read Readi ng data D ownload ing, controlling, and mon itoring all the nodes Download, Control and Monitor all ether link node Data Read Data Read Rea ding data Readi ng data 11.2.1.1 General Specifications and Functions 1. General specifications:
11-34 Item Specifications Communication type Distribution Data transfer rate 100 Mbps Communication medium Category 5 shielded cable Maximum transfer distance 100 meters Data storage Relays (A word is taken as a unit.), data registers, and link registers Number of storage blocks Maximum of 128 blocks Size of a storage block Maximum of 1900 words Modules supported AHCPU530-EN, AH10EN-5A