Delta Electronics AH500 — 12.4.1 CPU Modules

Chapter 12 Troubleshooting 12.4 Error Codes and LED Indicators A. Columns a. Error code: If the error occurs in the system, the error code is generated. b. Description: The description of the error c. CPU status: If the error occurs, the CPU stops running, keeps running, or in the status defined by users.  Stop: The CPU stops running when the error occurs.  Continue: The CPU keeps running when the error occurs.  Self-defined: The status of the CPU can be defined by users. Please refer to section 8.2.1 in this manual for more information. d. LED indicator status: If the error occurs, the LED indicator is ON, OFF, or blinks.  ERROR: The system error  BUS FAULT:

The I/O bus error  Module ERROR: The module error  LED indicators 12.4.1 CPU Modules 12-41 LED indicator Description The status of the CPU ON: A serious error occurs in the system. ERROR OFF: The system is normal. Blinking: A slight error occurs in the system. CPU The status of the I/O bus ON: A serious error occurs in the I/O bus. BUS FAULT OFF: The I/O bus is normal. Blinking: A slight error occurs in the I/O bus. The status of the module ON: A serious error occurs in the module. Module ERROR OFF: The module is normal. Blinking: A slight error occurs in the module. Error code Description CPU Status LED indicator status ERROR BUS FAULT 16#000A Scan timeout (SM8:

The watchdog timer error) Stop Blinking Keep 16#000B The program in the PLC is damaged. Stop ON Keep 16#000C The program downloaded to the PLC is incorrect. Stop Blinking Keep 16#000D The CPU parameter is damaged. Stop ON Keep 16#000E The program or the parameter is being downloaded, and therefore the PLC can not run. Stop Blinking Keep 16#000F The original program in the PLC is damaged. Continue Keep Keep 16#0010 The access to the memory in the CPU is denied. Stop ON Keep 16#0011 The PLC ID is incorrect. (SM9) Continue ON Keep 16#0012 The PLC password is incorrect. Continue ON Keep 16#0013 The I/O module can not run/stop.

(SM10) Stop Keep ON 16#0014 The procedure of restoring the system can not be executed. (SM9) Stop ON ON 16#0015 The module table is incorrect. (SM10) Stop ON Keep 16#0016 The module setting is incorrect. (SM10) Stop ON Keep 16#0017 The device which is associated with the data register is incorrect. (SM10) Stop ON Keep 16#0018 The serial port is abnormal. (SM9) Continue Blinking Keep 16#0019 The USB is abnormal. (SM9) Continue Blinking Keep