Delta Electronics AH500 — 12.4.1 CPU Modules

AH500 Operation Manual 12-44 Error code Description CPU Status LED indicator status ERROR BUS FAULT 16#2010 1. The instruction does not support the device. 2. Encoding error 3. The instruction is a 16-bit instruction, but the constant operand is a 32-bit code. (SM5) Stop Blinking Keep 16#2011 The number of operands is incorrect. (SM5) Stop Blinking Keep 16#2012 Incorrect division operation (SM0/SM5). Self-defined Blinking Keep 16#2013 The value exceeds the range of values which can be represented by the floating-point numbers. (SM0/SM5) Self-defined Blinking Keep 16#2014 The task designated by TKON/YKOFF is incorrect, or exceeds the range.

(SM5) Stop Blinking Keep 16#2015 There are more than 32 levels of nested program structures supported by CALL. (SM0) Self-defined Blinking Keep 16#2016 There are more than 32 levels of nested program structures supported by FOR/NEXT. (SM0/SM5) Self-defined Blinking Keep 16#2017 The number of times FOR is used is different from the number of times NEXT is used. (SM5) Stop Blinking Keep 16#2018 There is a label after FEND, but there is no SRET. There is SRET, but there is no label. (SM5) Stop Blinking Keep 16#2019 The interrupt task is not after FEND. (SM5) Stop Blinking Keep 16#201A IRET/SRET is not after FEND. (SM5) Stop Blinking Keep 16#201B There is an interrupt task, but there is no IRET.

There is IRET, but there is not interrupt task. (SM5) Stop Blinking Keep 16#201C End is not at the end of the program. (SM5) Stop Blinking Keep 16#201D There is CALL, but there is no MAR. (SM5) Stop Blinking Keep 16#201E The function code used in MODRW is incorrect. (SM102/SM103) Self-defined Blinking Keep 16#201F The length of the data set in MODRW is incorrect. (SM102/SM103) Self-defined Blinking Keep 16#2020 The communication command received by using MODRW is incorrect. (SM102/SM103) Self-defined Blinking Keep 16#2021 The checksum of the command received is incorrect.

(SM102/SM103) Self-defined Blinking Keep 16#2022 The format of the command used in MODRW does not conform to the ASCII format. (SM102/SM103) Self-defined Blinking Keep 16#2023 There is a communication timeout when MODRW is executed. (SM120/SM103) Self-defined Blinking Keep 16#2024 The setting value of the communication timeout is invalid. (SM120/SM103) Self-defined Blinking Keep 16#2025 There is a communication timeout when RS is executed. (SM120/SM103) Self-defined Blinking Keep 16#2026 The interrupt number used in RS is incorrect. Self-defined Blinking Keep 16#2027 The execution of FWD is abnormal. (SM102/103) Self-defined Blinking Keep 16#2028 The execution of REV is abnormal.

(SM102/103) Self-defined Blinking Keep 16#2029 The execution of STOP is abnormal. (SM102/103) Self-defined Blinking Keep 16#202A The execution of RSDT is abnormal. (SM102/103) Self-defined Blinking Keep 16#202B The execution of RSTEF is abnormal. (SM102/103) Self-defined Blinking Keep 16#202C I/O interrupt service routine 0 does not exist. Stop Blinking Keep 16#202D I/O interrupt service routine 1 does not exist. Stop Blinking Keep 16#202E I/O interrupt service routine 2 does not exist. Stop Blinking Keep