Delta Electronics AH500 — 12.4.1 CPU Modules

Chapter 12 Troubleshooting 12-43 Error code Description CPU Status LED indicator status ERROR BUS FAULT 16#0064 The file in the memory card can not be read. (SM453) Continue Keep Keep 16#0065 The file in the memory card is a read-only file. (SM453) Continue Keep Keep 16#0066 An error occurs when the system is backed up. Continue Blinking Keep 16#0067 The size of the PLC parameters restored exceeds the size of the PLC parameters of the CPU module. Continue Blinking Keep 16#1401 An error occurs when the data in the I/O module is accessed. (SM9) Stop Keep ON 16#1402 The actual arrangement of the I/O modules is not consistent with the module table.

(SM9) Stop Keep ON 16#1403 An error occurs when the data is read from the module. (SM9) Stop Keep ON 16#1404 A watchdog timer error occurs in the module. (SM9) Stop Keep ON 16#1405 The setting parameter of the module is not found. (SM9) Stop Keep ON 16#1407 A communication error occurs when the data is accessed through the auxiliary processor. (SM9) Continue ON Keep 16#1409 The extension backplane is disconnected. (SM9) Stop Keep ON 16#140A The communication with the extension backplane is incorrect. (SM9) Stop Keep ON 16#140B The number of network modules exceeds the limit. (SM9) Stop Keep ON 16#1801 There is no interrupt service routine in the CPU module.

Continue Keep Keep 16#2000 There is no END in the program in the PLC. (SM5) Stop Blinking Keep 16#2002 GOEND is used incorrectly. (SM5) Stop Blinking Keep 16#2003 The devices used in the program exceed the range. (SM0/SM5) Self-defined Blinking Keep 16#2004 The part of the program specified by the label used in CJ/JMP is incorrect, or the label is used repeatedly. (SM0/SM5) Stop Blinking Keep 16#2005 The N value used in MC is not the same as the corresponding N value used in MCR, or the number of N values used in MC is not the same as the number of N values used in MCR.

(SM5) Stop Blinking Keep 16#2006 The N values used in MC do not start from 0, or the N values used in MC are not continuous. (SM5) Stop Blinking Keep 16#2007 The operands used in ZRST are not used properly. (SM5) Stop Blinking Keep 16#200A Invalid instruction (SM5) Stop Blinking Keep 16#200B The operand n or the other constant operands exceed the range. (SM0/SM5) Self-defined Blinking Keep 16#200C The operands overlap. (SM0/SM5) Self-defined Blinking Keep 16#200D An error occurs when the binary number is converted into the binary-coded decimal number. (SM0/SM5) Self-defined Blinking Keep 16#200E The string does not end with 0x00.

(SM0/SM5) Self-defined Blinking Keep 16#200F The instruction does not support the modification by an index register. (SM5) Stop Blinking Keep