Delta Electronics — 6.2.4 AS04TC Control Registers

Chapter 6 Temperature Measurement Module AS04/08TC 6_ 6-9 CR# Name Description Defaults channel 3 217 The minimum peak value for channel 4 - 222 The time to record for channel 1 Unit: 100 ms Range: 1–100 The time to record the digital value for the channels 1 223 The time to record for channel 2 1 224 The time to record for channel 3 1 225 The time to record for channel 4 1 240 The number of records for channel 1 Range:

0-500, display the current records 0 241 The number of records for channel 2 0 242 The number of records for channel 3 0 243 The number of records for channel 4 0 4000- 4499 Records for channel 1 500 records for channel 1 -- 4500- 4999 Records for channel 2 500 records for channel 2 -- 5000- 5499 Records for channel 3 500 records for channel 3 -- 5500- 5999 Records for channel 4 500 records for channel 4 --