Delta Electronics — 6.2.7 Control Mode

Chapter 6 Temperature Measurement Module AS04/08TC 6_ Note: 1. If the PID parameter exceeds the upper limit, only the maximum value can be written in the module, if the PID parameter is below the lower limit, only the minimum value can be written in the module. 2. When PID_RUN switches from True to False, it clears the MV output value to 0. If you need to keep the last MV output value, you can swith the operand EN to False to close this instruction and the MV output value can be kept. 6-25 Operand Data type Function Setting range Description BIAS DWORD/DINT Feed forward output value -32768~32767 Feed forward output value, used for the PID feed forward.

CYCLE DWORD/DINT Sampling time (TS) 1~1000 (unit: 100 ms) When the instruction is scanned, use the PID algorithm according to the sampling time, and refresh MV. MV REAL MV output value 0.0~100.0 (unit: 1%) PV DWORD/DINT/REAL Present value Format is defined in HWCONFIG. I MV _ REAL Accumulated integral value Accumulated integral value is for reference. When the MV is out of the range of 0-100%, the accumulated integral value in I MV stops changing. _ ERROR DWORD/DINT Error / status codes 16#0000:instruction is being executed and is working normally 16#1400:the module you are using does not support this instruction.

16#1401:group number or module number setting error 16#1402:the module you are using does not respond and communication time out 16#1403:channel setting error