AS Series Module Manual Example 1. You need to set up the parameters before executing DMPID. Switch the operand EN from False to True to execute this instruction. If you need to change parameters during execution, you can use the UPDATE flag to update the parameters (including PID_RUN ~ CYCLE) . After the paraemters are updated, the system clears the flag UPDATE. 2. When M0 is ON, the instruction is executed. When M2 is ON, the DMPID starts to process. When M2 is OFF, MV value is 0. And the value in MV is stored in D16. When M0 is OFF, the instruction is not executed. And the values in the instruction is not changed. 3.
When the mode is set to 1, the system starts to auto tuning the parameters for the temperature control. After tuning is done, the sysem switches to auto control mode (PID_MODE is set to 0) and fill in the appropriate parameters (Kc_Kp, Ti_Ki, Td_Kd, Tf, ALPHA and BETA) to data devices. You can also use retentive devices to retain PID parameters. _6 6-26