Delta Electronics — 6.2.7 Control Mode

Chapter 6 Temperature Measurement Module AS04/08TC Use PID parameters 6_ 6-27 CR# Operand Function Description Range CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 600 630 660 690 720 750 780 810 PID RUN _ Enable the PID algorithm 1: the PID algorithm is implemented. 0: the output value (MV) is reset to 0, and the PID algorithm is not implemented. 0 601 631 661 691 721 751 781 811 SV SV Target value 0 602 632 662 692 722 752 782 812 PID MODE _ PID control mode 0: automatic control When PID MAN _ is switched from 1 to 0, the output value (MV) is included in the automatic algorithm. 1: the parameters are tuned automatically for the temperature control.

When the tuning is complete, the device is automatically reset to 0, and the parameters Kc _Kp, Ti _Ki, Td _Kd, and Tf are set 0