AS Series Module Manual _6 6-28 CR# Operand Function Description Range CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 appropriately. 603 633 663 693 723 753 783 813 PID MAN _ PID A/M mode 0: auto; the MV is output based on the PID algorithm. 1: manual; the MV is output based on the MOUT. When PID MODE is _ also set to 1, this setting is ineffective. 0 604 634 664 694 724 754 784 814 MOUT AUTO _ MOUT automatic change mode 0: normal; the MOUT does not vary with the MV. 1: auto; the MOUT varies with the MV. 0 605 635 665 695 725 755 785 815 Auto DBWA Auto tuning non-action zone Range: 0–32000, used when SV is in the ±dead band in auto tuning mode.
0 606 607 636 637 666 667 696 697 726 727 756 757 786 787 816 817 Kc Kp _ Calculated proportional coefficient (Kc or Kp) Kc Kp are _ floating-point numbers. If the P coefficient is less than 0, the Kc Kp _ is 0. Independently, if Kc Kp is 0, it is not _ controlled by P. 3.846