Chapter 6 Temperature Measurement Module AS04/08TC 6_ 6-31 CR# Operand Function Description Range CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 present difference is less than the absolute value of ERR DBW and it _ meets the cross status condition, the present error is counted as 0, and the PID algorithm is implemented. Otherwise the present error is brought into the PID algorithm normally. 618 648 678 708 738 768 798 828 α value Integral sum Range: 0–100 Unit: 0.01 31 619 649 679 709 739 769 799 829 β value Integral sum 0 620 650 680 710 740 770 800 830 MOUT Manual output value (MOUT) When PID MAN is _ set to 1, the MV value is output as this manual MOUT value, between MV MAX and _ MV MIN. _ Range:
0–1000 (0%–100%) 0 621 651 681 711 741 771 801 831 BIAS Feedforward output value Feedforward output value, used for the PID feedforward 0 622 623 652 653 682 683 712 713 742 743 772 773 802 803 832 833 MV Output value (MV) A floating-point number Range: 0–100 Unit: % --