Delta Electronics — 7.2.4 Control Registers

Chapter 7 Load Cell Module AS02LC 7_ 7-7 CR# Name Description Defaults 66 channel 2 Maximum measuring weight; when the weight measured exceeds the limit, an alarm is triggered. The value should be greater than 1. 67 Filter mode for channel 2 0: no filter (default) 1: maximum filter mode 2: average filter mode 0 68 Maximum filter for channel 2 Range: 0–8; the bigger the number the stronger the filter 1 69 Average weight measured times for channel 2 Range:

1–100 10 70 Upper limit of the zero return for channel 2 Floating-point format Determines the current weight as the zero point in the upper/lower range; when the lower range is larger than the upper range, the lower range is read as the upper range and vice versa. 10 71 72 Lower limit of the zero return for channel 2 -10 73 74 Zero point tracking time for channel 2 Range: 1–500 Unit: 100 ms 10 75 Zero point tracking range for channel 2 Floating-point format Range: 0–10000; 0: disabled 0 76 77 Calibration points for channel 2 Range: 2–20 2 78–117 Calibrated weight for channel 2 Floating-point format Calibrated weight of the calibration points 1–20 - 118 Decimal place for channel 1 Range:

0–4 1 119 Decimal place for channel 2 Range: 0–4 1 120 Alarm 0: warning 1: alarm Bit1: error in the power supply Bit2: error in the module hardware Bit3: error in the driver board 0 200 State register Refer to the explanation below. - 201 Instruction set Refer to the explanation below. 0 210 The maximum peak value Floating-point format -