Chapter 7 Load Cell Module AS02LC Normal Exchange Area Explanation You can view the error code, the channel value, and the state code, as well as the data registers that correspond to their instructions on the Normal Exchange Area tab of the Device Setting dialog box in the HWCONFIG utility in ISPSoft. CR#200: Codes for the state register Explanation 7_ 7-9 Bit Code Definition Bit Code Definition b0 16#0001 Error exists in the power supply. b1 16#0002 Error exists in the module hardware. b2 16#0004 Error exists in the driver board.
b3 16#0008 Calibration disabled b4 16#0010 Reserved b5 16#0020 Reserved b6 16#0040 The weight measured by CH1 exceeds the maximum weight that can be measured, or the voltage of SEN is incorrect. b7 16#0080 The weight measured by CH2 exceeds the maximum weight that can be measured, or the voltage of SEN is incorrect. b8 16#0100 The weight measured by CH1 exceeds the maximum weight b9 16#0200 The weight measured by CH2 exceeds the