Chapter 8 Serial Communication Module AS00SCM 8.3 COM mode This section introduces communication modes of AS00SCM-A module (firmware V2.00) when the communication protocol is Modbus, UD Link or CANopen. 8.3.1 Modbus The AS00SCM-A supports standard communication protocols such as Modbus RS232, RS422, and RS485. Once you create a data exchange table, you can exchange data with slave modules. You can set up communication format and node ID via HWCONFIG. Refer to section 8.2.2 for more details. When AS00SCM-A acts as scanner/master, you can create a data exchange table and exchange data with slave modules. To initialize Modbus communication: Open HWCONFIG.
-> Set up the node ID and communication format. -> Create a data exchange table. -> Select a Mode (Program Control, PLC Run, or Always Enable). -> Download HWCONFIG. -> Enable this function. Refer to section 8.3 in AS Series Operation Manual for more details. When AS00SCM acts as adapter/slave, it provides a communication channel for AS series PLC to read and write. Supporting function codes and addresses are shown below. Addresses and corresponding registers for function card 1 / 2 8_ Corresponding data registers can be obtained when AS series PLC uses AS00SCM-A for communication and via HWCONFIG to set up. Refer to section 8.6.1 for more details.
8-9 Function Code Attribute Supporting addresses 0x03 0x04 Read 16#0000~16#0063 16#0100~16#0163 16#0200~16#0263 16#0300~16#0363 0x06 0x10 Write 16#0000~16#0063 16#0200~16#0263 0x17 Read 16#0000~16#0063 16#0100~16#0163 16#0200~16#0263 16#0300~16#0363 Write 16#0000~16#0063 16#0200~16#0263 Funciton cards Address for data to Length (character) Address for data to Length (character) be written be read Function card 1 16#0000 100 16#0100 100 Function card 2 16#0200 100 16#0300 100