AS Series Module Manual Ground Ground (2) The 24 VDC cable should be twisted pair, and the shorter end should be connected to the module. (3) The cable (110 VAC, 220 VAC, and 24 VDC) must not be installed near a main circuit, a high-voltage cable, or a cable connected to a load that is not a PLC. In addition, the cable must not be bound to a main circuit, a high-voltage cable, or a cable connected to a load that is not a PLC. All the cables should be wired at least 100 mm apart. (4) Ground the power supply using a 14 AWG wire. (5) Connect 20–14 AWG (1 mm) wires to the input/output terminals. Use only copper leads that can resist temperatures above 60° C /75° C.
_8 8.2.3.2 AS00SCM-A Communication Interface COM mode: This module comes with two function card slots, supporting AS-F232, AS-F422, and AS-F485 communication cards. The card 2 slot also supports the AS-FCOPM communication card when the firmware is V2.00 or later. Refer to Chapter 9 for more information about wiring the cards. RTU mode: The card 2 slot supports the AS-FCOPM communication card when the firmware is V2.00 or later and supports AS-FEN02 when the firmware is V2.02. For wiring information, refer to Chapter 9. 8-8 SCM AS Series IO DC Power Supply 24VDC Min 1.5A 0V 24V Ground Ground 24V DC Power Supply 24VDC 0V Ground SCM AS Series IO DC Power Supply 24VDC 24V Other devices