Delta Electronics — 8.4.1 CANopen Mode (AS-FCOPM)

AS Series Module Manual 8.4 RTU Mode 8.4.1 CANopen Mode (AS-FCOPM) When the function card AS-FCOPM works with an AS series PLC, it supports three kinds of RTU modes, including AS Remote Communication, CANopen DS301 Mode and Delta Special Driver & AS Remote Mode. Use the switch FORMAT 1 to switch among three RTU modes. A. RTU Communication Mode Setup Switch “ FORMAT 1 ” B. Node ID Setup Switch “ ID1/ID2 ”  ID1: 0 (recommended)  ID2: 0 (the switch is no function; set up through ISPSoft); see the table below for the switch setting range. C. RTU Communication Speed Setup Switch “ FORMAT 2 ” Use the switch for setting.

You cannot use ISPSoft (HWCONFIG) to set up the communication mode in this format. _8 8-16 FORMAT1 Description 0 AS Remote Communication 4 CANopen DS301 8 Delta Special Driver & AS Remote Mode RTU mode ID2 setting range AS Remote Communication 1~F (by the number of slaves) Delta Special Driver & AS Remote Mode 1~F (by the number of slaves) CANopen DS301 1~F (if the switch is at 0, the setting range is set by HWCONFIG) FORMAT2 1 2 3 4 5 6 7 8-F Byte (bps) 10K 20K 50K 125K 250K 500K 1000K NA Distance (m) 5000 2500 1000 500 250 100 25 NA