Delta Electronics — 8.4.1.1 AS Remote Communication Mode

Chapter 8 Serial Communication Module AS00SCM 8.4.1.1 AS Remote Communication Mode  Double-click the AS Series PLC, then in Device Setting click Function Card 2 Setting and set the function card module and set up the baud rate. After the setting is done, download the parameters. 2 to AS-FCOPM, set to working mode to AS Remote Communication Mode, enter the number of the AS remote Turn the FORMAT1 switch to 0 and it is in AS Remote Communication Mode. In AS Remote Communication mode, an AS series CPU PLC can connect to as many as 15 AS00SCM-A modules, as long as they are all in RTU mode. The RTU station number should be set from 1 to 15 in numerical order.

RTU mode and baud rate cannot be set via ISPSoft (HWCONFIG). Use the switch ID2 to set up Node ID and use the switch FORMAT2 to set up the baud rate. (The baud rate should be the same as the PLC’s baud rate.) 8_ Steps for a quick setup 1. Set up the PLC: AS Remote Communication mode, number of the device: 1; baud rate: 1000kbps; download the parameters. 2. Set up AS00SCM-A; set the ID1 switch to 0 and FORMAT1 to 0; ID2 switch to 1 and FORMAT2 to 7. 8-17