Delta Electronics — 8.4.1.2 Delta Special Driver & AS Remote Mode

AS Series Module Manual 3. Supply power to AS00SCM-A and connect AS00SCM-A to the PLC with a CANopen cable. 4. Resupply power to the PLC and the indicator of CARD2 should keep blinking. That indicates AS00SCM-A and the PLC are connected. The PLC error indicator should be blinking too, since the setting is not done yet. 5. Use HWCONFIG to scan the connected devices to see if AS00SCM-A is connected. 6. Download the parameters and check if the PLC error indicator has stopped blinking. Then the setting of one RTU device is complete.

8.4.1.2 Delta Special Driver & AS Remote Mode  Double-click the AS Series PLC, then in Device Setting click Function Card 2 Setting and set the function card 2 to AS-FCOPM, set to working mode to Delta Special Driver & AS Remote Mode and enter the number of the AS remote module and set up the baud rate. After the setting is done, download the parameters. _8 Turn the FORMAT1 switch to 8, and it is in Delta Special Driver & AS Remote Mode. In this mode, an AS series CPU PLC can connect to as many as 7 AS00SCM-A modules, as long as they are all in RTU mode. The RTU station number should be set from 9 to 15 in numerical order. RTU mode and baud rate cannot be set via ISPSoft (HWCONFIG).

Use the switch ID2 to set up Node ID and use the switch FORMAT2 to set up the baud rate. (The baud rate should be the same as the PLC’s baud rate.) 8-18