Chapter 8 Serial Communication Module AS00SCM Steps for a quick setup 1. Set up the PLC: Delta Special Driver & AS Remote Mode m mode, number of the device: 1; baud rate: 1000kbps; download the parameters. 2. Set up AS00SCM-A; set the ID1 switch to 0 and FORMAT1 to 8; ID2 switch to 9 and FORMAT2 to 7. 3. Supply power to AS00SCM-A and connect AS00SCM-A to the PLC with a CANopen cable. 4. Resupply power to the PLC and the indicator of CARD2 should keep blinking. That indicates AS00SCM-A and the PLC are connected. The PLC error indicator should be blinking too, since the setting is not done yet. 5. Use HWCONFIG to scan the connected devices to see if AS00SCM-A is connected. 6.
Download the parameters and check if the PLC error indicator has stopped blinking. Then the setting of one RTU device is complete. 8.4.1.3 CANopen DS301 Mode This mode supports AS Series PLC acts as the CPU and the 3 rd party CANopen DS301 devices (non-AS series devices and non-Delta PLC). When using Delta PLC as the CPU, you need to use CANopen Builder to set up. Before using a 3 rd party PLC, use AS Series PLC as the CPU and select the AS Remote Communication Mode. Before connecting to CANopen DS301, turn the AS00SCM-A FORMAT1 switch to 4, and the adjustable range for station knob ID2 becomes 0x1 h ~0xF h . This mode is used to communicate with a Master PLC from other brand.
See the detail in section 8.6.3. when the PDO data is mapped, AS00SCM-A can control the IO modules from its right side. 8_ Double-click the AS Series PLC, then in Device Setting click Function Card 2 Setting and set the function card 2 to AS-FCOPM, set to working mode to CANopen DS301. 8-19