AS Series Module Manual Steps for a quick setup 1. Set up the PLC: in AS Remote Communication Mode, connect AS series PLC to AS00SCM-A, refer to section 8.4.1.1 for more details. 2. Use AS series PLC to scan the I/O modules installed on the right-side of AS00SCM-A and download the parameters. 3. If using HWCONFIG to set up the node ID, you can use COM mode to connect AS00SCM-A to the right-side of AS series PLC directly and no I/O module behind it. Use AS series PLC’s HWCONFIG to scan and add AS00SCM-A in and then double-click the module to set up its node ID and then download the parameters. After that, switch ID2 to 0. 4.
Install the I/O module to the right side of AS00SCM-A and switch the working mode to RTU. 5. Switch FORMAT1 to 4 and use the CANopen cable to connect to the PLC, and then supply power to AS series PLC. Refer to section 8.6.3 PDO examples, if you are using AH10COPM-5A as the CPU. 6. Follow master’s CANopen setting method to install the slaves. 8.4.2 EtherNet/IP Mode AS00SCM-A (firmware V2.02 or later) can be installed on AS-FEN02. However it can only be used in RTU mode and you can use Delta PLC or the 3 rd party EtherNet/IP device to control the right-side modules of the AS00SCM-A. Refer to section 9.2.7 for more details on the operations of AS-FEN02 installed on AS Series PLC.
_8 8.4.2.1 Connecting to Delta PLC Scanner through EIP Builder Through EIP Builder, an AS Series PLC (when acting as a scanner) can create an EtherNet/IP connection to AS00SCM-A (when installed) on AS-FEN02. Below shows an example of AS Series PLC acting as a scanner to create an EIP connection. 8-20