AS Series Module Manual 9.1 Introduction Function cards are extension cards such as analog input/output (AI/AO) and communication cards for the AS Series PLC. 9.2 Specification and Function 9.2.1 AS-F232 communication other interfaces such as RS-232, PC, and so on. Except for the communication interface, however, the The AS Series PLC is built with COM1 (RS-485) and COM2 (RS-485) ports. You can use the AS-F232 extension card for communication functions are the same as the built-in ones. You can set up the communication port as either a slave or a master node. After installing the extension card, use HWCONFIG in ISPSoft to configure the communication.
Wiring example AS-F232 (DB9 female) + + Superior machine 9.2.2 AS-F422 DB9 male to DB9 female (standard cable) Use the AS-F422 extension card to communicate with Delta HMI devices or other devices that use an RS-422 communication port. Other than the different communication interface, the communication functions remain the same as the built-in ones. You can set the communication port as either a slave or a master node. After installing the extension card, use HWCONFIG in ISPSoft to configure the communication. Wiring example for communication with Delta HMI DOPA series via COM2 AS-F422 Delta HMI series DOPA 9.2.3 AS-F485 COM2/DB-9 master node.
After installing the extension card, use HWCONFIG in ISPSoft to configure the communication. With its own standalone communication port, the AS-F485 card can work independently and can be either a slave or a Wiring example Master node Slave node Slave node Terminal resistor (120 ohm) Terminal resistor (120 ohm) 9-2 1 2 3 4 R+ Tx+ 3 6 RT 4 7 RT 2 8 1 9 CT CT S- R- Tx- S+ S+ T+ Rx+ T- Rx- S- D+ D - SG D+ D- SG SG D+ D- 9 _ Shielded cable