Delta Electronics — 9.2.5 AS-F2DA

Chapter 9 Function Cards 9.2.4 AS-F2AD 2 analog signal input channels: Use the program to read the values in SR to obtain the corresponding A/D conversion value for the channel. 9.2.5 AS-F2DA 2 analog signal output channels: Use the MOV instruction to move the value to the SR to obtain the corresponding voltage output value.

9_ 9-3 Item Voltage Input Current Input Analog Signal DC 0 V - 10 V DC 4 mA - 20 mA Resolution 12-bit 11-bit Input Impedance 2 MΩ 250 Ω Conversion Time 3 ms / CH Characteristic Curve 4000 Output Value Digital 0 10V Voltage input 2000 Output Value Digital 4 20mA Current input Digital Value Output Card 1 SR168 (CH1) SR169 (CH2) Card 2 SR170 (CH1) SR171 (CH2) Item Voltage Output Current Output Analog Signal DC 0 V - 10 V DC 4 mA - 20 mA Resolution 12-bit 12-bit Impedance Allowance ≥1 kΩ ≤500 Ω Conversion Time 2ms / CH Characteristic Curve 10V Output Voltage 0 4000 Digital Value Input 20mA Output Current 4 4000 Digital Value Input Digital Value Output Card 1 SR172 (CH1) SR173 (CH2) Card 2 SR174 (CH1) SR175 (CH2)