AS Series Module Manual 10.4.9 LED Indicators and Troubleshooting AS01DNET-A has two LED indicators and one digital displayer. NS LED and MS LED display the connection status of AS01DNET-A. The digital displayer shows the node address and error information of AS01DNET-A as well as error information of the slave. 10.4.9.1. NS LED 10.4.9.2. MS LED 10 10-36 01DNET LED status Indication Correction OFF No power; Or duplicate ID check has not been completed. 1. Check if AS01DNET-A is powered and the connection is normal. 2. Make sure that at least one node can communicate normally. Green light blinking (ON:0.5s and OFF: 0.5s alternately) The connection to the DeviceNet network failed.
No correction; Refer to Digital Displayer for troubleshooting. Green light ON Online; The connection to the DeviceNet network is normal. No correction Red light blinking (ON:0.5s and OFF: 0.5s alternately) Communication error Refer to Digital Displayer for troubleshooting. Red light ON Network trouble, duplicate node ID, no network power or Bus-OFF. 1. Make sure that all the devices in the network have their unique node addresses. 2. Check if the network installation is correct. 3. Check if the baud rates of the master and slave are same. 4. Check if the network power is normal.
LED status Indication Correction OFF No power Make sure that the power supply for AS01DNET-A is normal and the connection is proper. Green light blinking (ON:0.5s and OFF: 0.5s alternately) No module is configured. Configure the scan list and then download the configuration to AS01DNET. Green light ON Input and output data are normal. -- Red light blinking (ON:0.5s and When AS01DNET works as the master, the slave in Scan List can not Refer to Digital Displayer. Make sure that the slave information in Scan List