Chapter 10 DeviceNet Master Scanner Module AS01DNET-A 10.4.9.3. Combination of MS LED and NS LED 10.4.9.4. Digital Displayer 10 10-37 LED status Indication Correction OFF: 0.5s alternately) work normally. When AS01DNET works as the slave, an error occurs in the configuration. matches that of the actually connected slave. Red light ON An error inside AS01DNET 1. Check if the configuration is correct. 2. Return the module to factory for repair if the error still exists after repower ON. LED status Indication Correction NS LED MS LED OFF OFF No power Check if the power supply for AS01DNET-A is normal. OFF Green light ON Duplicate ID check has not been completed.
Make sure that the baud rate of at least one node in the network is the same as that of the module and their communication is normal. Red light ON Green light ON Duplicate ID check failed or Bus-OFF. 1. Ensure that the node ID of AS01DNET is unique. 2. Repower the module. Red light ON Red light blinking (ON:0.5s and OFF: 0.5s alternately) No network power 1. Check if the network cable connection is proper. 2. Check if the network power supply is normal. Red light ON Red light ON Hardware error Return the module to the factory for repair. Code Explanation Correction 0~63 Node address of AS01DNET-A (in normal operation) -- 80 AS01DNET-A is in STOP status.
Turn the PLC to RUN and start I/O data exchange F0 The node ID of AS01DNET is the same as that of other node or exceeds the allowed range. 1. Ensure that the node address of AS01DNET is unique. 2. Re-power AS01DNET. F1 No slave is configured in Scan List. Configure the scan list and then download the configuration to AS01DNET. F2 Too low voltage of the work power Check if the power supply for AS01DNET and the PLC is normal. F3 AS01DNET enters the test mode Switch the function switch IN1 from On to Off and re-power AS01DNET-A. F4 BUS-OFF 1. Check if the network cable is normal and the shielded cable is grounded. 2. Check if the baud rates of all nodes in the network are same. 3.
Check if the start and end of the network cable are both connected with a 121Ω terminal resistor. 4. Re-power AS01DNET-A. F5 No network power 1. Check if the network cable is normal. 2. Ensure that the network power is normal. F6 Internal error; Flash or RAM If the error still exists after re-power, send AS01DNET-A back to the