AS Series Module Manual 10.5.5.3. Using LD Program to Control the Entire Network Program Explanation: 1. In network 1, write a value for the output of AS16AP and for the output of channel 1 of AS04DA when M0 changes to ON. 2. In network 2, move the input value of AS16AP to D0 and the input value of channel 1 of AS04AD to D1 when M1 changes to ON. 10.5.6 Error Diagnosis and Trouble Shooting AS01DNET (RTU) provides four diagnosis methods such as LED indicator, seven-segment displayer, status word diagnosis and software diagnosis. 10.5.6.1.
Indicator Diagnosis NS indicator 10 10-90 LED status Indication How to deal with OFF No power supply; Or the repeated node ID detection has not been completed. 1. Check the power supply for AS01DNET (RTU) and the connection are normal. 2. Make sure that the baud rates of AS01DNET (RTU) and the master match. Green light blinking (ON:0.5s and OFF: 0.5s alternately) No connection between AS01DNET (RTU) and its right-side modules Configure AS01DNET (RTU) in the DeviceNet software and download the configuration correctly. Green light ON Normal I/O data transmission between AS01DNET (RTU) and DeviceNet master No correction needed