Chapter 10 DeviceNet Master Scanner Module AS01DNET-A MS indicator 10.5.6.2. Codes in Seven-Segment Displayer 10 10-91 LED status Indication How to deal with Red light blinking (ON:0.5s and OFF: 0.5s alternately) I/O connection timeout between AS01DNET (RTU) and DeviceNet master Refer to the error shooting in Codes in Seven-Segment Displayer below. Red light ON Network trouble; Repeated node ID; No network power; Or BUS-OFF. 1. Ensure that the IDs of all nodes are unique on the bus. 2. Check if the network installation is normal. 3. Check if the baud rate of AS01DNET (RTU) is the same as that of the bus. 4. Check if the node ID of AS01DNET (RTU) is valid. 5.
Check if the network power supply is normal. LED status Indication How to deal with OFF No power Check if the power supply for AS01DNET (RTU) and connection are normal. Green light blinking (ON:0.5s and OFF: 0.5s alternately) 1. AS01DNET (RTU) is waiting for the I/O data from DeviceNet master. 2. No I/O data transmission between AS01DNET(RTU) and DeviceNet master 3. The PLC connected to DeviceNet master is in STOP state. 1. Configure AS01DNET (RTU) in the DeviceNet software and download the configuration correctly. 2. Switch the PLC to RUN state Green light ON Normal transmission of I/O data between AS01DNET (RTU) and DeviceNet master No correction needed Red light blinking (ON:0.5s and OFF:
0.5s alternately) No network power supply; Configuration error; Module alarms. 1. Check if the network power supply is normal; 2. Reset the internal parameters in AS01DNET (RTU); 3. Check if there is an error or alarm in the I/O modules connected to the right side of AS01DNET (RTU). Red light ON Hardware error Return the product to factory for repair if the error still exists after re-power on. Code Indication How to deal with 0~63 Node ID of the scanner module (When in RUN state) No correction needed F0 The node ID is repeated or exceeds allowed range. 1. Ensure that the node ID of AS01DNET (RTU) is unique in the DeviceNet network within the range of 0~63. 2.
Repower it on after changing the node ID. F1 No I/O module is configured to AS01DNET (RTU) in the DeviceNet Builder software. Add I/O modules in AS01DNET (RTU) in the DeviceNet Builder software and download the configuration data to AS01DNET (RTU) after the configuration is finished. F2 The work voltage of AS01DNET (RTU) is too low. Check if the power supply for AS01DNET (RTU) works normally.